title: ${DOCUMENT_TITLE}
|
||
author: ${AUTHOR_NAME}
|
||
date: \today{}
|
||
mainfont: Avenir Next
|
||
documentclass: article
|
||
fontsize: 12pt
|
||
# NOTE: The applegreen is a custom color defined in resources/head.tex
|
||
linkcolor: applegreen
|
||
urlcolor: applegreen
|
||
abstract: |
|
||
**Prepared For:**
|
||
|
||
${CUSTOMER_NAME}
|
||
|
||
${CUSTOMER_STREET}
|
||
${CUSTOMER_CITY_STATE_ZIP}
|
||
|
||
```{=latex}
|
||
\begin{center}
|
||
```
|
||
<!-- below are just forced line breaks -->
|
||
\
|
||
\
|
||
\
|
||
|
||
[{ width=30% }](${COMPANY_WEBSITE})
|
||
|
||
```{=latex}
|
||
\end{center}
|
||
```
|
||
---
|
||
|
||
<!-- NOTE: Table of contents section only needs changed if new sections are
|
||
added.
|
||
-->
|
||
|
||
# Contents
|
||
|
||
1. [Introduction](#home-performance-report)
|
||
1. [Your Goals](#your-goals)
|
||
1. [Leakage](#how-leaky-is-your-house)
|
||
1. [Observations](#observations)
|
||
1. [HVAC](#hvac-observations)
|
||
1. [Home](#home-observations)
|
||
1. [Load Calculations](#load-calculations)
|
||
1. [Your Loads](#your-loads)
|
||
1. [Airflow Assessment](#airflow-assessment)
|
||
1. [Your Static Measurements](#your-static-measurements)
|
||
1. [Static Pressure Forecast](#static-measurements-forecast)
|
||
1. [Summary](#summary)
|
||
1. [Definitions](#definitions)
|
||
1. [CFM50]
|
||
1. [IAQ]
|
||
1. [LAIR]
|
||
1. [Load Calculation][load-calculation]
|
||
1. [Shell][shell]
|
||
1. [SHR]
|
||
1. [TESP]
|
||
1. [WC][wc]
|
||
|
||
# Home Performance Report
|
||
|
||
Thank you for having us to your home for a home performance assessment. I hope that it was
|
||
beneficial. We learned a lot about your home and your goals during the brief visit. So, let’s jump
|
||
in to some of the things discovered.
|
||
|
||
Below is a summary of your goals, house measurements, and our budget discussion as well as my
|
||
observations and some recommendations. As part of the service we ran load calculations that help
|
||
determine the right sized HVAC for your home as it stand and with some upgrades. Those are attached
|
||
as are bids for replacements.
|
||
|
||
Once you read the report you’ll have 3 options: do nothing, pick and choose upgrades, or do more
|
||
planning for more difficult goals or complex projects. These options are discussed at the end of the
|
||
report as well as our leanings for your home.
|
||
|
||
\goalsimage
|
||
|
||
## Your goals:
|
||
|
||
<!-- NOTE: This should probably be a table in most cases, with a rank.-->
|
||
|
||
<!--
|
||
| Goal | Rank |
|
||
| ------ | ---- |
|
||
| A goal | 8 |
|
||
| B goal | 5 |
|
||
-->
|
||
<!-- WARNING: Add goals here -->
|
||
|
||
1. Add air conditioning.
|
||
|
||
# How Leaky Is Your House
|
||
|
||
<!-- NOTE: Several of the variables used in this section are defined in vars.sh
|
||
Do not change them here, instead update them in the vars.sh file.
|
||
-->
|
||
|
||
One of the main objectives was to perform a blower door test and load calculations for the home. We
|
||
discovered that the blower door number was
|
||
${HOME_LEAKAGE} [CFM50] for the approximately ${HOME_SQUARE_FEET} \squarefoot (${HOME_LAIR} [LAIR]).
|
||
A leaky home, most often, is an uncomfortable and uncontrollable home.
|
||
|
||
> _Air leakage tends to have one of the largest impacts on the load of a home._
|
||
>
|
||
> - _Around 1:1 homes begin to be more controllable / comfortable_
|
||
> - _Your home is ${HOME_LEAKAGE}:${HOME_SQUARE_FEET} \squarefoot for a ratio of ${HOME_LAIR}_
|
||
> - _Leaky homes are very difficult to maintain comfort with HVAC alone._
|
||
|
||
# Observations
|
||
|
||
The below sections are observations about the current HVAC system and the home.
|
||
|
||
## HVAC Observations
|
||
|
||
<!-- WARNING: Add HVAC observations here. -->
|
||
|
||
1. Current furnace is sized appropriately based on the load of the home.
|
||
1. Current duct system is not sized adequately for the system.
|
||
1. Filter is too small for the system.
|
||
1. Return sizing is not adequate.
|
||
1. Supply sizing is marginal.
|
||
1. Current static pressure is already high.
|
||
1. These problems may become worse when AC is installed.
|
||
|
||
## Home Observations
|
||
|
||
<!-- WARNING: Add house observations here. -->
|
||
|
||
1. The house leakage is high for the size of the home.
|
||
1. May be hard to control comfort without [shell] improvements.
|
||
|
||
# Load Calculations
|
||
|
||
Several [load-calculations][load-calculation] were performed on your home to determine the proper
|
||
equipment sizing for this application. Below is a comparison of the
|
||
[load-calculations][load-calculation] with the current air leakage and several improved air leakage
|
||
targets.
|
||
|
||
## Your Loads
|
||
|
||
<!-- WARNING: Add the project loads here. -->
|
||
|
||
| [CFM50] | | Heating Total | Cooling Total | [SHR] | [LAIR] |
|
||
| ------------------- | ----------- | ------------- | ------------- | -------- | ---------------- |
|
||
| **${HOME_LEAKAGE}** | **Current** | **55,102** | **20,726** | **0.79** | **${HOME_LAIR}** |
|
||
| 2,000 | | 40,320 | 17,279 | 0.85 | 1.5:1 |
|
||
| 1,350 | | 35,885 | 16,245 | 0.88 | 1:1 |
|
||
|
||
> **Note:**
|
||
>
|
||
> 1. _The lower the heating and cooling total's the better._
|
||
> 1. _An undersized air conditioner is better than an oversized one._
|
||
> 1. _Supplemental dehumidification may be required for [SHR]'s below 0.83._
|
||
|
||
The above table shows the relationship between air leakage and the amount of heating and cooling
|
||
that is required for the home. A tight home is easier to control the comfort levels, offers superior
|
||
IAQ levels, and lower utility costs.
|
||
|
||
<!-- WARNING: Update this summary for the given project -->
|
||
|
||
The projected cooling size required for your home is around 2-Tons for the current leakage rate, or
|
||
1.5-Tons if [shell] improvements were made.
|
||
|
||
[Here is a link to your load calculation reports][loads-folder]
|
||
|
||
# Airflow Assessment
|
||
|
||
While on site, we also measured the total system airflow and static pressure of the system. Static
|
||
pressure is equivalent to the blood pressure of your system and gives us a better understanding of
|
||
the overall ability for the system to provide the proper amount of airflow, as well as how much it
|
||
may struggle to do so.
|
||
|
||
Static pressure is the amount of resistance that the blower has to work against in order to move air
|
||
through the system. Things that have an effect on the static pressure of the system include, air
|
||
filters (size and type), duct sizes, amount of ducts, length of ducts, duct fittings and
|
||
transitions, as well as internal system components. Each component of the system has a resistance
|
||
associated with it that the blower has to overcome, by taking some key measurements we are able to
|
||
determine the [TESP] of the system. While there are several static pressures in the system, when we
|
||
talk about static pressure we are generally referring to [TESP].
|
||
|
||
Static pressure ([TESP]) has a range of _low_, _acceptable_, or _high_. While these numbers are
|
||
specific to the actual equipment, most manufacturers follow similar standards. For the sake of
|
||
simplicity, 0.5" [wc] or under is an _acceptable_ target, 0.8" [wc] is generally the max acceptable
|
||
static pressure (although we like to stay well below this if possible), and above 0.8" [wc] is
|
||
considered _high_ and should be addressed. _Low_ is generally not common and is rarely problematic,
|
||
so it is not focused on much.
|
||
|
||
<!-- NOTE: Force a new page here, for images and sub-section heading to be on same page -->
|
||
|
||
\newpage
|
||
|
||
## Your Static Measurements
|
||
|
||
![True Flow Report][trueflow-image]{ height=50% }
|
||
|
||
<!-- WARNING: Summarize the static measurements here -->
|
||
|
||
The above image is a snapshot of the static pressures recorded for your system. This shows that the
|
||
static pressure of your system is very high (1.114" [wc]). The primary culprits for the high static
|
||
pressure are that the filter is undersized for the airflow required and the return duct sizing is
|
||
small.
|
||
|
||
These measurements were taken in the heating mode because your system does not currently have air
|
||
conditioning. Currently the heating airflow is on the low side for what is required for your system
|
||
(1200 CFM would be ideal). This should be adjusted if possible during the install to get better
|
||
performance and efficiency out of the system, given that some static pressures can be improved
|
||
during the project.
|
||
|
||
\
|
||
\
|
||
|
||
[Here is a link to the full airflow report.][trueflow-file]
|
||
|
||
<!-- NOTE: Force a new page here, for images and sub-section heading to be on same page -->
|
||
|
||
\newpage
|
||
|
||
## Static Measurements Forecast
|
||
|
||
![True Flow Forecast][trueflow-forecast-image]{ height=50% }
|
||
|
||
<!-- WARNING: Summarize the forecast results below. -->
|
||
|
||
The above image is a snapshot is of a forecast of the static pressures after adding air
|
||
conditioning. It should be noted that these measurements are based solely on the airflow required
|
||
for cooling mode, not for heating mode (in other words, heating mode is going to be higher because
|
||
the airflow requirement is higher).
|
||
|
||
This shows that with an upgraded filter we can get the static pressure below the 0.8" [wc] max
|
||
target while in cooling mode.
|
||
|
||
\
|
||
\
|
||
|
||
[Here is a link to the full forecast report.][trueflow-forecast-file]
|
||
|
||
# Summary
|
||
|
||
The purpose of the home performance assessment is to help find the overlap between the house needs,
|
||
the goals, and the budget to see if there's a viable project.
|
||
|
||
<!-- WARNING: Add summary here -->
|
||
|
||
The house is pretty leaky overall. This is due to the age and construction style of the house. This
|
||
may lead to comfort problems or trouble maintaining comfort in all areas of the house.
|
||
|
||
Based on the [load calculations][load-calculation], the previously quoted systems are too large for
|
||
the current load, so we need to update the proposals to be for 2-Ton systems. This will help with
|
||
the fact that the static pressure of the system is already really high. The static pressure for
|
||
heating will likely still be above the 0.8" [wc] max threshold.
|
||
|
||
An upgraded air filter is going to be required to help alleviate the blower motor. Another return
|
||
may be required in the living space to further drop the static pressure, however this could likely
|
||
be done in the future if desired. I would estimate that adding another return would be in the
|
||
**$800-1,200** range.
|
||
|
||
While on site it was mentioned that you would like some of the ducts to be sealed that go to the
|
||
second floor. This is something that is not included in our general proposals. I would estimate this
|
||
to be an additional **$150-300** and will add options in the updated proposals.
|
||
|
||
Since the goal is to add air conditioning, then I would recommend going with a 2-Ton system. If the
|
||
system does not maintain then you could look into [shell] improvements and air sealing the home.
|
||
|
||
Regards,
|
||
|
||
\
|
||
\
|
||
\
|
||
|
||
[Here is a link to all the documents][document-folder]
|
||
|
||
<!-- NOTE: These are reference links for short form linking in the document.
|
||
This allows all the links to be changed / updated in one place.
|
||
However most do not need updated unless sections are added, besides the
|
||
document links, which are defined / setup in vars.sh.
|
||
-->
|
||
|
||
[CFM50]: #cfm50-definition "CFM50"
|
||
[IAQ]: #iaq-definition "IAQ"
|
||
[LAIR]: #lair-definition "LAIR"
|
||
[load-calculation]: #load-calculation-definition "load calculation"
|
||
[shell]: #shell-definition "shell"
|
||
[SHR]: #shr-definition "SHR"
|
||
[wc]: #wc-definition "wc"
|
||
[TESP]: #tesp-definition "TESP"
|
||
|
||
<!-- prettier-ignore-start -->
|
||
|
||
<!-- IMPORTANT: Take screen shots of the TrueFlow reports and add to the img
|
||
folder with names / path setup in vars.sh -->
|
||
|
||
<!-- default is img/trueflow.png -->
|
||
[trueflow-image]: ${TRUEFLOW_IMAGE}
|
||
|
||
<!-- default is img/forecast.png -->
|
||
[trueflow-forecast-image]: ${TRUEFLOW_FORECAST_IMAGE}
|
||
<!-- prettier-ignore-end -->
|
||
|
||
<!-- NOTE: These links are defined in vars.sh -->
|
||
|
||
[loads-folder]: ${LOADS_FOLDER}
|
||
[trueflow-file]: ${TRUEFLOW_FILE}
|
||
[trueflow-forecast-file]: ${TRUEFLOW_FORECAST_FILE}
|
||
[document-folder]: ${DOCUMENT_FOLDER}
|