tags: HVAC, hydronics, chiller
|
||||
---
|
||||
|
||||
# Heat Recovery Chiller
|
||||
|
||||
This is an article that I wrote back in 2020, but I don't believe that I published it anywhere, so
|
||||
I'm doing it now. I did discuss this on
|
||||
[this episode of the HVAC School Podcast.](https://hvacrschool.com/podcasts/is-the-future-of-air-conditioning-self-contained-propane-chillers/)
|
||||
|
||||
## Heat Recovery Chillers
|
||||
|
||||
I have always had a love and passion for hydronic systems, perhaps it's because they are not that
|
||||
common in most areas. The designs tend to be elegant and the flexibility is unparalleled by most
|
||||
equipment choices currently available in the U.S. I'm going to try to not get too far into the weeds
|
||||
in this article, but offer an overview of what I feel would be my dream system.
|
||||
|
||||
## The Source
|
||||
|
||||
A heat recovery chiller will do simultaneous heating and cooling, as opposed to a traditional
|
||||
heat-pump or reverse cycle chiller that can only operate in one mode at a time. This system would
|
||||
have a second refrigerant to water heat exchanger and utilize the air-source when we don't need to
|
||||
bank / store heat, or are running in heat only mode. There are several benefits to this style
|
||||
system, the main being that while operating simultaneous heating / cooling mode the COP of the
|
||||
system doubles. For example, the [Multi-Aqua MHRC2](https://multiaqua.com/mhrc2/) shows a COP of
|
||||
about 8, which is approximately equivalent to 30 EER or 34 SEER. This gives us geothermal level
|
||||
performance without the need of a field.
|
||||
|
||||
## Indoor Portion
|
||||
|
||||
The indoor portion of the system, we would utilize buffer tanks as thermal storage for the chiller.
|
||||
The buffer tanks give us several benefits, including longer run times for the chiller, load
|
||||
matching, and the ability to size for larger load (heating or cooling) without some of the problems
|
||||
that occur when over-sizing a traditional system. The buffer tanks also allow sizing more
|
||||
aggressively by having storage during peak load conditions.
|
||||
|
||||

|
||||
|
||||
This shows a cooling buffer tank as well as a heating buffer tank. The horizontal pumps are what
|
||||
circulate water through the chiller, while the vertical pumps are what distribute the water to the
|
||||
load / emitters. This configuration allows for water to be used for the loads first and extra
|
||||
capacity to go into the buffer tanks. The buffer tanks also offer hydraulic separation for the pumps
|
||||
(meaning that they won't interfere with each other if / when there are different flow rates).
|
||||
Another advantage of the buffer tanks is that you can connect multiple heating or cooling sources in
|
||||
parallel to the system. This is shown by the extra tees in the hot buffer tank where we could
|
||||
connect something such as solar water collectors, pellet or wood boiler, or a conventional boiler.
|
||||
You'll also notice on the right side of the hot buffer tank, that I am showing a brazed plate heat
|
||||
exchanger that would be used to supply domestic hot water.
|
||||
|
||||
## Distribution System
|
||||
|
||||
This could be a number of things, from radiant panels, in-floor, high-output baseboard radiators,
|
||||
however I'm going to model it as a 4-pipe hydronic air handler.
|
||||
|
||||

|
||||
|
||||
The hydronic air handler is able to provide cooling, heating, and re-heat dehumidification, all in
|
||||
one package. With a hydronic system, it would be very easy to load match by controlling the fan
|
||||
speed and utilizing a Delta-T pump or outdoor reset controls. These air handlers are available from
|
||||
several manufacturers and come in different styles from traditional (as shown), small duct high
|
||||
velocity systems, and even ductless styles.
|
||||
|
||||
## Disadvantages
|
||||
|
||||
1. Not highly available in the U.S.
|
||||
1. When the chiller is down nothing works (not much different than traditional)
|
||||
1. Lack of understanding / technicians afraid to work on this style system.
|
||||
1. Potentially higher upfront costs.
|
||||
1. Lack of design or planning could cause unhappy clients (same with traditional)
|
||||
1. Distribution systems need to be designed around low water temperatures (not a drop in replacement
|
||||
for traditional boiler systems)
|
||||
|
||||
## Advantages
|
||||
|
||||
1. Central plant for heating, cooling, and DHW (also a disadvantage)
|
||||
1. Flexible distribution options / methods.
|
||||
1. Self contained refrigerant circuit
|
||||
1. Ability to produce / store thermal energy during off peak electrical hours
|
||||
1. Ability to move BTU's more efficiently through water than air
|
||||
1. Long life for distribution system (50-100+ years)
|
||||
1. Easier transition to natural / flammable refrigerants
|
||||
|
||||
## Conclusion
|
||||
|
||||
In conclusion, there are many advantages to this style system, as well as disadvantages. One of the
|
||||
main points is to think of the system in 3 distinct components, the source(s), thermal storage, and
|
||||
distribution. As mentioned, this only one concept, but in reality, there are many ways to accomplish
|
||||
this, which is one of it's advantages. For example, perhaps in certain scenarios it makes sense to
|
||||
dump excess heat into a pool, create ice storage during off peak hours, cascade into another water
|
||||
-> water heat pump for higher temperature distribution, incorporate solar collectors, and so on.
|
||||
|
||||
Thank you for reading all the way to the end!
|
||||